Our site services team can provide a full condition survey on your existing AHU plant. Typically, we would cover the following areas during a condition survey on an AHU.
Casework
Check all internal and external casework for corrosion. Check all panels for air leakage. Check all panels for ingress of rain water. Check rain roofs are correctly allowing water to run from the top of the AHU and not allowing rain water to form puddles.
Louvres / Cowls
Check for integrity and ensuring they are fit for purpose.
Dampers
Ensure they operate smoothly and correctly and check functional properties of the damper actuators where fitted.
Filters
Check for condition of the filters and the filter slide frames / casework. Check for evidence of incoming rain water possibly damaging the filters due to high velocities on the AHU inlet. Check for damage / wear to the filter slide frames or mechanisms deployed for holding of the filters.
Fans / Motors
Check mechanical and electrical properties. Check impellors turn freely and there are no signs of bearing damage. Check the anti-vibration mountings and flexible connections for signs of wear / damage.
Coils
Check the coil fins for any signs of blockages. Inspect the coil fins (particularly frost coils) for any crumbling of the fins. Check condition of the pipework for any previous signs of leakage. Inspect drain trays and traps.
Thermal Wheels
Ensure there are no mechanical defects with the thermal wheel. Check to ensure no damage has been caused to the wheel matrix and check for signs of blockages (particularly on systems that have had poorly maintained filters as dirty air may have passed through the unit into the wheel matrix). Check the speed controller functions correctly.
Plate Heat Exchangers
Visibly check for any possible damage to the heat exchanger surfaces and structure. Check for signs of blockages (particularly on systems that have had poorly maintained filters as dirty air may have passed through the unit into the heat exchanger matrix). Check that the by-pass damper turns freely and observe the condition of the by-pass damper.
Unit B & C Kirkgate Business Centre, Chantry Bridge, Wakefield, WF1 5DL • 01924253509
Copyright ©
CLP Air Group Ltd. CLP Air Group Ltd is registered in England & Wales: No. 03772225.
Website made in Yorkshire with care by Marmalade Digital